Permit: T12CM01581

Parcel: 14016003B


Addresses:

5085 S CHERRY AV


Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T12CM01581

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/31/2012 FIRE - FINAL Approved IMC 508 NO MAKE UP AIR WAS INSTALLED WHEN HOOD SYSTEM WAS.
IMC 507.2.1.1 NO HEAT SENSOR TO TURN ON EXHAUST FAN WHEN COOKING IS BEING DONE.
10/22/2012 FIRE - FINAL Not ready for Inspection Same as last inspection
09/07/2012 FIRE - FINAL Denied Final will not be given until old hood extinguisher permit is completed (permit # T06BU00793); permit was never called in for the final acceptance testing. I did the sprinkler final 09/07/2012 and found that the hood extinguisher system was installed and ready to go. Found out from the contractor that they had to do some welding on the hood because of holes and united fire install new gas valve and electrical.
NOTE: Will need to have hood extinguisher system monitored by the fire system.