Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T12CM01581
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/31/2012 | FIRE - FINAL | Approved | IMC 508 NO MAKE UP AIR WAS INSTALLED WHEN HOOD SYSTEM WAS. IMC 507.2.1.1 NO HEAT SENSOR TO TURN ON EXHAUST FAN WHEN COOKING IS BEING DONE. |
|
10/22/2012 | FIRE - FINAL | Not ready for Inspection | Same as last inspection | |
09/07/2012 | FIRE - FINAL | Denied | Final will not be given until old hood extinguisher permit is completed (permit # T06BU00793); permit was never called in for the final acceptance testing. I did the sprinkler final 09/07/2012 and found that the hood extinguisher system was installed and ready to go. Found out from the contractor that they had to do some welding on the hood because of holes and united fire install new gas valve and electrical. NOTE: Will need to have hood extinguisher system monitored by the fire system. |