Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - KITCHEN EXH HOOD FINAL
Permit Number - T12CM01581
Inspection Description - FIRE - KITCHEN EXH HOOD FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/31/2012 | FIRE - KITCHEN EXH HOOD FINAL | Approved | IMC 508 NO MAKE UP AIR WAS INSTALLED WHEN HOOD SYSTEM WAS. IMC 507.2.1.1 NO HEAT SENSOR TO TURN ON EXHAUST FAN WHEN COOKING IS BEING DONE. |
|
10/22/2012 | FIRE - KITCHEN EXH HOOD FINAL | Denied | Final will not be given until old hood extinguisher permit is completed (permit # T06BU00793); permit was never called in for the final acceptance testing. |