Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
12/20/2012 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
12/14/2012 MECHANICAL - INTERMEDIATE Partial Approval 1) CONDENSATE CAN NOT TERMINATE AT WASTE VENT.
2) PVC IS TO BE SUPPORTED UP OFF OF ROOF A MIN. OF 1.5", ALL PUC EXPOSED TO DAY LIGHTS IS TO BE CCATED FOR U.V. PROTECTION.
3) CONDUIT IS IN DISREPAIR ON ROOF.
4) IF WHITE WIRE IS USED ASA GROUND, STRIP BARE OR CCAT WITH GREEN IDENTIFICATION
5) UNIT NOT PROPERLY SUPPORTED ON ROOF.
06/28/2012 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
06/27/2012 MECHANICAL - INTERMEDIATE Cancelled
06/26/2012 MECHANICAL - INTERMEDIATE Denied 1. PROVIDE SAFE ACCESS TO ROOF.
2. PROVIDE 1" CLEARANCE B-VENT FROM COMBUSTIBLES
3. INSULATE DUCT WORK IN NON-CONDITIONED SPACE
4. 2" INSULATION ROOF TOP INSULATION
5. LABEL PERMANENT MAIN DISCONNECT