Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T12CM01550
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/20/2012 | PLUMBING - FINAL | Approved | ||
06/19/2012 | PLUMBING - FINAL | Not ready for Inspection | 1. Missing clean-out at sink. 2. Ice maker and ice bin drains may not be combined. IW drain more than five feet to be directly trapped.. Use purple primer as well as solvent cement. 3. One inch air gap a must. 4. Finish insulation at water heater. 5. Backflow certification. Clean bacteria report, method of sterilization. | |
06/18/2012 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* |