Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T12CM01457
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/31/2012 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
05/10/2012 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) I.D. INVERTERS 1 & 2, ALSO CKT BRKRS IN COMBINER PANEL 2) CORRECTION PER NOTE #2 NOT INSTALLED IN WORKMANSHIP LIKE MANOR-CONNECTORS/CONDUIT NOT SEATED CORRECTLY |
|
05/04/2012 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED ACCESS INTO CARPORT-NO ANSWER AT FRONT DOOR 2) USE PROPER FITTINGS FOR CONNECTION FROM AC DISC. SW. TO SERVICE PANEL 110.12 NEC 3) ONLY ONE CONDUCTOR PER TERMINATION ONTO GROUND BAR PER LISTING OF PANEL 110.3 NEC |