Permit: T12CM01453

Parcel: 12702242A


Addresses:

5147 E 2ND ST

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
04/04/2012 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
04/02/2012 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) 12" OF COVER, MINIMUM REQUIRED
2) RELIEF DRAIN IS REQUIRED TO BE OF MATERIALS APPROVED FOR WATER HEATER
3) REPLACE DAMAGED VALVE
4) EACH JOINT OF VENT REQUIRES MINIMUM 2 GALVE SCREWS
5) FILL ALL HOLES
6) BOND WATER PIPE TO GAS PIPE
7) PROVIDE ROOF ACCESS
03/30/2012 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) FACTORY COATED PIPING REQUIRED BELOW GRADE
2) 10 PSI TEST WITH A 15 PSI GAUGE REQUIRED
3) B-VENT IS UPSIDE DOWN AND REQUIRES 1" CLEARANCE SECURE CONNECTORS
4) TERMINATE RELIEF DRAIN OUTSIDE
5) PROVIDE ACCESS TO ROOF, FLASHING AND SUPPORTS
6) BOND GAS TO WATER