| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/04/2012 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) NOTE HIGH LEG MARKINGS AND LABELS |
|
| 04/03/2012 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) BOND SERVICE RISER 250.92 2) NEED REJECTION PINS 3) CLEAN SURFACE UNDER LUG 250.12 4) SECURE PANELS TO STRUCTURE 5) SECURE UNIT STRUT TO ROOF 6) TIGHTEN LOOSE TERMINATIONS 7) CHECK FOR DERATING |