Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T12CM01382

Parcel: 11204205B

Inspection Status: Partial Approval

Inspection History: ELECTRIC - SERVICE UPGRADE

Permit Number - T12CM01382

Inspection Description - ELECTRIC - SERVICE UPGRADE

Inspection Status - Partial Approval

Date Description Inspector Results Comments
04/04/2012 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*
1) NOTE HIGH LEG MARKINGS AND LABELS
04/03/2012 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*
1) BOND SERVICE RISER 250.92
2) NEED REJECTION PINS
3) CLEAN SURFACE UNDER LUG 250.12
4) SECURE PANELS TO STRUCTURE
5) SECURE UNIT STRUT TO ROOF
6) TIGHTEN LOOSE TERMINATIONS
7) CHECK FOR DERATING