Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/21/2012 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 09/25/2012 | ELECTRIC - INTERMEDIATE | Denied | 1. VERIFY/GROUNDING ELETRODE SYSTEM 250.50+250.58 AND WATER AND GAS BONDS 2. NEED ALL/FAULT CALCULATIONS TO VERIFY SERVICE REQUIREMENTS 3. BOND SERVICE NIPPLES 4. FINISH 3 PHASE RUN TO TEP TRANSFORMER 5. LABEL SERVICE EQUIPMENT 6. CAN NOT USE SES AS JUNCTION BOX OR PASS THRU FOR NEW SERIVCE |