Permit: T12CM01373

Parcel: 138043610


Addresses:

841 W CALLE BOCINA

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
05/25/2012 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
05/24/2012 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
1) COMPLY WITH PREVIOUS NOTES
2) CLAY PIPE OK PER LEERAY HANLY
05/23/2012 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
1) AT WATER CLOSET: WHERE IS VENT CONNECTS TO A HORIZONTAL DRAIN, IT SHALL HAVE ITS INVERT TAKEN OFF ABOVE THE DRAINAGE CENTER LINE, DOWN STREAM OF THE TRAP. EACH VENT SHALL RISE VERTICALLY, TO A POINT NOT LESS THAN 6" ABOVE THE FLOOD RIM BEFORE OFF SETTING HORIZONTALLY
2) AT SHOWER: EACH FIXTURE TRAP TO HAVE VENT. A DRAIN MAY NOT DAMP INTO A VENT
3) A FURNCO MAY NOT BE USED UNDER THE FLOOR
4) CLAY PIPE IS NOT PERMITTED UNDER THE FLOOR
05/21/2012 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*