Inspection Status: Approved
Inspection History: BUILDING - PROGRESS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/20/2012 | BUILDING - PROGRESS | Approved | IVRS - Inspection :* | |
| 10/24/2012 | BUILDING - PROGRESS | Partial Approval | EXCEPT NOTES 2+8 FROM PREVIOUS | |
| 10/18/2012 | BUILDING - PROGRESS | Denied | NOTES 1-3, & 7-8 ON PREVIOUS INSPECTION | |
| 08/10/2012 | BUILDING - PROGRESS | Partial Approval | SHEET ROCK NAILING BATHROOM OK | |
| 08/02/2012 | BUILDING - PROGRESS | Partial Approval | 1) SHEET ROCK NAILING IN DINING ROOM AND MASTER BATHROOM OK | |
| 07/24/2012 | BUILDING - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 07/03/2012 | BUILDING - PROGRESS | Not ready for Inspection | IVRS - Inspection :* PROVIDE TEST ABS |
|
| 06/19/2012 | BUILDING - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 05/21/2012 | BUILDING - PROGRESS | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE PROPERTY PINS TO VERIFY 20" SET BACK CARPORT COLLAR TIES OR LU26 HANGERS H2.5 RAFTER TO BEAM AT CARPORT 2) REAR PORCH HEADER 4 X 6 OVER SPANNED. ADD POSTS. EXPOSE FOOTERS TO VERIFY DEPTH. LU26 A FASCIA ATTACHMENT WITH FHA STRAP 3) ADD NEW KITCHEN ELECTRICAL TO PLAN. EXPOSE FOR INSPECTION 4) PROVIDE 10' HEAD TEST ALL ABS ROUGH SOIL 5) BATH ELECTRICAL NOT READY 6) EXPOSE ELECTRICAL IN SUITE OR PROVIDE LETTER HEAD FROM LICENSED ELECTRICAL CONTRACTOR STATING ALL WORK TO CODE FOR SAFETY 7) EXPOSE WALL TO RAFTER CONNECTIONS 8) CONSULT WITH TEP CABLE DROP AT REAR PORCH 30" ROOF FLAT |