Permit: T12CM01371

Parcel: 13613027F

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
05/01/2012 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
04/19/2012 MECHANICAL - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
INFORMATION ONLY AS PER TOM COLLINS
04/12/2012 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) #3 PROVIDE APPROVED GAS PIPE SUPPORTS AND SECURE PIPING
2) #4 PROTECT SUPPORT AND SECURE CONDENSATE PIPING.NOTE PVC PRIMER IS REQUIRED
3) #1 INSTALLATION MAY NOT BLOCK WATER HEATER ACCESS-RELOCATE
4) #2 NEED TO SEE GAS SUPPLY CONNECTION TO GAS MAIN PIPING. MAY NEED A PSI TEST
5) LIST MAY NOT BE COMPLETE