Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/06/2012 | MECHANICAL - FINAL | Approved | WORK FOR NEW SUB PANEL AND WIRE NOT PERMITTED NOTICE TO FOLLOW | |
| 06/21/2012 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 04/18/2012 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* YOU CANNOT USE THE AIR CONDITIONING ELEC CIRCUIT TO POWER THE SERVICE RECEPTACLE. PROVIDE A BUSHING IN ELEC DISCONNECT. PROVIDE MIN 8-2" DUCT LINER IN ALL EXPOSED DUCT ON ROOF |
|
| 04/06/2012 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) INSTALL ? VOLT RECEPT NEXT TO ROOF TOP UNIT 2) PAINT PVC CONDENSATE DRAIN 3) INSIDE OK NOTE TO OWNER: IF YOU WANT TO TRY-REMOVE GALVANIZED TRAP ARM AND INSTALL ABS TRAP ARM. 1 1/2" SLXMIP ADPT 1 1/2" SWEEP AND PIPE AT 2 PERCENT GRADE |