Permit: T12CM01367

Parcel: 127051850


Addresses:

4844 E 3RD ST

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
08/06/2012 MECHANICAL - FINAL Approved WORK FOR NEW SUB PANEL AND WIRE NOT PERMITTED NOTICE TO FOLLOW
06/21/2012 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
04/18/2012 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
YOU CANNOT USE THE AIR CONDITIONING ELEC CIRCUIT TO POWER THE SERVICE RECEPTACLE.
PROVIDE A BUSHING IN ELEC DISCONNECT.
PROVIDE MIN 8-2" DUCT LINER IN ALL EXPOSED DUCT ON ROOF
04/06/2012 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
1) INSTALL ? VOLT RECEPT NEXT TO ROOF TOP UNIT
2) PAINT PVC CONDENSATE DRAIN
3) INSIDE OK
NOTE TO OWNER: IF YOU WANT TO TRY-REMOVE GALVANIZED TRAP ARM AND INSTALL ABS TRAP ARM. 1 1/2" SLXMIP ADPT 1 1/2" SWEEP AND PIPE AT 2 PERCENT GRADE