Permit: T12CM01341

Parcel: 141311060

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Permit Number - T12CM01341

Inspection Description - BUILDING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/27/2012 BUILDING - FINAL Approved
06/26/2012 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*
LEAK UNDER MASTER CAVITORY
CONDENSATE IS BACK PITCHES AT UNIT. WATER DRAIN PAN
SUPPORT ALL PVC CLOSE TO CONNECTION. GET METAL PAN OFF PVC STILL HAVE OUTLETS MORE THAN 1/4' FROM SHEET ROCK FACE.
KS NOT SEALED ON BACKSIDE UNDER GRANITE 1/2 CU AT HB REQ INSULATION
06/25/2012 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*
PROPERLY TERMINATE GROUNDING CONDUCTER AT AC DISCONNECT
TIGHTEN CONDUIT CONNECTION.
CORRECT WH CONDUIT STRAP
CORRECT BOXES MORE THAN A 1/4" @ NON COMBUSTIBLE.
ID PANEL - NO CABREVATIONS
PROVIDE A ROMEX CONNECTER AT ATTIC DISCONNECT MAINLAIN WORKING CLEARANCE, MIN 36"
TURN WATER HEATER ON FOR INSP.
SUPPORT DRAIN PAN & CONDENSATE PIPING
SUPPORT LINE SET IN ATTIC, PROTECT FROM UV EXPOSURE