Permit: T12CM01334

Parcel: 12801005H

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T12CM01334

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
08/20/2012 PLUMBING - INTERMEDIATE Approved
08/07/2012 PLUMBING - INTERMEDIATE Not ready for Inspection COMPLETE ALL WORK SHOWN, PROVIDE REVISIONS, PLAN SPECS STORILIZATION, MIXING VALVES, ROOF TOP HB. 3 COMP SINK NOT INSTALLED PER PLAN. BACKFLOW ROTECTION WITH CERT REQUIRED AT HUMIDIFIER. THERMOMETERS SHOWN FOR WATER HEATERS
PROVIDE DRAINAGE FITTINGS AT TRAP ARMS.
CAULD DFS
REMOVE CONDENSATE CONNECTION FROM WH ROLLER DRAIN.
FS MISSING GRATE.
06/25/2012 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
INSTALL A TOUP HB VACUUM BREAKER
NEW HAND SINK PIPING OK, PROVIDE A COT PLAN REV
06/22/2012 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
06/12/2012 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
BREAK ROOM SINK AND CONDENSATE LINES CONDENSATE LINE FOR HUMIDOR OK TO COVER WALLS
06/08/2012 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
06/06/2012 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
06/05/2012 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*