Permit: T12CM01334

Parcel: 12801005H

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T12CM01334

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/21/2012 ELECTRIC - FINAL Approved
08/20/2012 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
08/17/2012 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
TRAINING ROOM
1. CORDS NOT ALLOWED ABOVE CEILING 400.7 & 8
2. SUPPORT TRACK 1 PER 4' OF TRACK 410.
1. SUPPORT VDV RACE WAYS PER CODE
2. NEED DISCONNECTING MEANS A/C UNIT IN HUMIDOR
3. FINISH #3,4 & 7 LAST INSPECTION
4. LISTING LABEL TO BE ON EQUIPMENT FROM FACTORY. FIELD INSTALLED TO BE DONE BY 3RD PARTY NRTL
08/14/2012 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) EM FIXTURE TO BE SUPPORTED OTHER THAN EMT CONDUIT
2) SUPPORT CONDUITS ABOVE SHELVES
3) SEAL COOLER AND HUMIDORS PER 300.7
3) VERIFY LISTING AND LABELING FOR HUMIDIFIERS, CASHIER STANDS, LIGHTING CONTRACTORS
5) BONDING 250.97 W/H DISCONNECT
6) NEED ARC FLASK LABELING
7) PANEL DIRECTORIES TO BE PER 408.4 AND LABEL PANELS TRASFORMER:
8) SUPPORT FLEX AND TIGHTEN LOOSE FITTINGS AT TRANSFORMER, BOND BUSHING, LOOSE TERMINATION, SPACIN OF LUGS
9) CLEAN EXCESS DIRT AND FOREIGN MATERIAL FROM BOTTOM OF PANEL
10) INPECTION STOPPED