Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T12CM01334
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/21/2012 | ELECTRIC - FINAL | Approved | ||
08/20/2012 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
08/17/2012 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* TRAINING ROOM 1. CORDS NOT ALLOWED ABOVE CEILING 400.7 & 8 2. SUPPORT TRACK 1 PER 4' OF TRACK 410. 1. SUPPORT VDV RACE WAYS PER CODE 2. NEED DISCONNECTING MEANS A/C UNIT IN HUMIDOR 3. FINISH #3,4 & 7 LAST INSPECTION 4. LISTING LABEL TO BE ON EQUIPMENT FROM FACTORY. FIELD INSTALLED TO BE DONE BY 3RD PARTY NRTL |
|
08/14/2012 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) EM FIXTURE TO BE SUPPORTED OTHER THAN EMT CONDUIT 2) SUPPORT CONDUITS ABOVE SHELVES 3) SEAL COOLER AND HUMIDORS PER 300.7 3) VERIFY LISTING AND LABELING FOR HUMIDIFIERS, CASHIER STANDS, LIGHTING CONTRACTORS 5) BONDING 250.97 W/H DISCONNECT 6) NEED ARC FLASK LABELING 7) PANEL DIRECTORIES TO BE PER 408.4 AND LABEL PANELS TRASFORMER: 8) SUPPORT FLEX AND TIGHTEN LOOSE FITTINGS AT TRANSFORMER, BOND BUSHING, LOOSE TERMINATION, SPACIN OF LUGS 9) CLEAN EXCESS DIRT AND FOREIGN MATERIAL FROM BOTTOM OF PANEL 10) INPECTION STOPPED |