Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T12CM01297
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/30/2012 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
03/28/2012 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) SEE NOTE #5 ON PAGE 2 2) 2006 UPC REQUIRES OPEN FRONT SEATS CHAPTER 4 3) ADA REQUIRES THAT PUSH BUTTON LAV FAUCETS USE LESS THEN 5 POUNDS TO OPERATE |
|