Inspection History: FIRE SPKLR - FINAL

Date Description Inspector Results Comments
01/08/2013 FIRE SPKLR - FINAL Approved
11/07/2012 FIRE SPKLR - FINAL Partial Approval FIX THE FUEL LEAK TO FIRE PUMP
Brace all 21/2" hose connections
Install inspectors test valve on riser #1 by battery charging station
Label all tamper valves per the call out on the fire panel
Sign the riser room door
Have a clean fire panel showing no problems
Install tampers for the outside OS&Y's for sprinkler system.
Fix water leaks on supply line to sprinkler system outside by the OSY valve.
11/05/2012 FIRE SPKLR - FINAL Denied Need tampers on outside OS&Y's.
Brace inspectors test valve for canopy area.
Brace all 2 1/2" hose connections
Install inspector test valve for riser #1 by battery station
Install riser room sign on riser door
Need jocky pump install or chang plans removing pump from system.