Permit: T12CM01291

Parcel: 132166450


Addresses:

4600 S PARK AV #06


Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T12CM01291

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/03/2012 FIRE - FINAL Approved
04/23/2012 FIRE - FINAL Denied 1. In supply room sprinkler head to close to wall needs to be 4 inches or more away.
2. In mechanical room remove tape from sprinkler head
3. Replace insulation that has falling down and or missing in the trusses sprinkler heads will be to far down from deck if no insulation,
4. Fire sprinkler and 5 year check valve reports are pass due, you will not get final until all inspection reports are up to date.