Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T12CM01291
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/03/2012 | FIRE - FINAL | Approved | ||
04/23/2012 | FIRE - FINAL | Denied | 1. In supply room sprinkler head to close to wall needs to be 4 inches or more away. 2. In mechanical room remove tape from sprinkler head 3. Replace insulation that has falling down and or missing in the trusses sprinkler heads will be to far down from deck if no insulation, 4. Fire sprinkler and 5 year check valve reports are pass due, you will not get final until all inspection reports are up to date. |