Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
Permit Number - T12CM01236
Inspection Description - ELECTRIC - RECONNECT
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/26/2012 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
03/21/2012 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CONDENSOR DISCONNECT MISSING COVER PLATE 2) SECURE LIQUID TIGHT EXPOSED CONDUCTORS CONDENSOR DISCONNECT 3) SMOKE ALARM BEDROOMS 4) SUB PANEL MIXED BREAKER TYPE MUST BE SIEMENS BREAKERS 5) 14 GAUGE WIRE ON 20 AMP BREAKER LIGHTING CIRCUIT |