Permit: T12CM01236

Parcel: 11942006L

Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Permit Number - T12CM01236

Inspection Description - ELECTRIC - RECONNECT

Inspection Status - Approved

Date Description Inspector Results Comments
03/26/2012 ELECTRIC - RECONNECT Approved IVRS - Inspection :*
03/21/2012 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CONDENSOR DISCONNECT MISSING COVER PLATE
2) SECURE LIQUID TIGHT EXPOSED CONDUCTORS CONDENSOR DISCONNECT
3) SMOKE ALARM BEDROOMS
4) SUB PANEL MIXED BREAKER TYPE MUST BE SIEMENS BREAKERS
5) 14 GAUGE WIRE ON 20 AMP BREAKER LIGHTING CIRCUIT