Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/20/2012 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
| 03/20/2012 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) WIRE NUT AND BLANK COVER NEEDED OVER OPEN BOX IN CARPORT 2) REPLACE MISSING COVER PLATES AND BROKEN COVER PLATES 3) SECURE WIRING IN WASHER SHED TO CODE 4) PHYSICAL PROTECTION ON CONDUCTORS BELOW 7' NEEDED IN SHED OR REMOVE WIRING 5) BLANK OFF OPEN BREAKER SPACES AT DEAD FRONT OF PANEL 6) ACCESS TO SHED AT SOUTH SIDE OF HOUSE TO INSPECTION WIRING OR REMOVE ELECTRICAL FROM SHED 7) SMOKE DETECTORS NEEDED IN ALL BEDROOMS AND ADJACENT HALL 8) REPLACE BROKEN 30 AMP BREAKER IN PANEL |