Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/21/2012 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 05/10/2012 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 05/02/2012 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) REPLACE DAMAGED VENT CONNECTOR 2) CONTRACTOR SHALL PAY REINSPECTION FEE |
|
| 04/27/2012 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) 12:10 PM-NO ONE HOME 2) PLEASE RESCHEDULE AT YOUR CONVENIENCE |
|
| 04/11/2012 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) VENT CONNECTOR STILL NOT SLOPED MINIMUM 1/4" PER FT 2) REMOVE FOIL TAPE AND SECURE ALL JOINTS WITH SCREWS 3) TAPED JOINT IN BACKWARDS 4) GAS FLEX CONNECTOR CANNOT EXCEED 3' TO WATER HEATER 5) PEX STILL RESTING ON SHARP METAL EDGE IN ENCLOSURE 6) INSULATION NOT SEFURED AT TERMINATION THRU COMBUSTION AIR VENT 7) SECURE BROKEN SCREEN AT VENT |
|
| 03/26/2012 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CORRECT SLOPE OF VENT CONNECTOR, PROVIDE PROPER ALIGNMENT OF DRAFT COLLAR AND SECURE ALL CONNECTIONS 2) PROVIDE A CODE APPROVED GAS SHUT OFF VALVE 3) PROVIDE 18" OF METALIC TUBING BETWEEN PEX AND WATER HEATER 4) SUPPORT TUBING AND PROTECT FROM METAL 5) PEX AND INSULATION REQUIRE CLEARANCE FROM HEAT SOURCE 6) CORRECT LEAK, AT STORAGE TANK 7) PATCH ROOF AND CORRECT INSULATION |