Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/13/2012 | ELECTRIC - FINAL | Denied | IVRS - Inspection : A reinspection fee has been assessed for this inspection. Multiple inspectio 1) SEALING AT BOTTOM IS NOT CODE COMPLIANT PLEASE PAY REINSPECTION FEE BEFORE NEXT INSPECTION |
|
| 07/12/2012 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) WHITE TAPE TO ENCIRCLE CONDUCTOR 200.6 (.3) (3) 2) SILICONE NOT AN APPROVED METHOD 110.12, 110.3 (B) 3) CLEAN SURFACE UNDER GROUND JUMPER 4) WE NOW HAVE LOOSE FITTINGS AT REWORKED RECPITCAL BOX |
|
| 07/06/2012 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 06/28/2012 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 04/10/2012 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) EXPOSE GROUND RODS FOR INSPECTION 2) BOND SHOULD HIT WATER SERVICE 1ST THEN GAS PIPE 3) COMPLETE ALL WORK TO CODE |
|
| 03/28/2012 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) ON FINAL TO SEE BRANCH CIRCUITS |