Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/16/2012 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/13/2012 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) REAR PORCH LIGHT NOT INSTALLED PER CODE (EXPOSED ROMEX) 2) USE FITTINGS APPROVED FOR EXTERIOR USE ON OUTDOOR CONDUIT FEEDING DRYER OUTLET 3) ELECTRIC OUTLET FOR DRYER NOT PROPERLY SECURED TO BLDG 4) OUTLET FOR COOLER TO HAVE WEATHER PROOF COVER 5) THIS IS AN UNGROUNDED SYSTEM, REPLACE ALL GROUNDED OUTLETS WITH (2 PRONG) UNGROUNEDED OUTLETS EXCEPT KITCHEN COUNTER OUTLETS TO BE GFI 6) ALL BEDROOMS AND AREAS LEADKING TO BEDROOMS ARE TO HAVE SMOKE ALARMS |