Permit: T12CM01009

Parcel: 106060180


Addresses:

1328 W PRINCE RD


Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Permit Number - T12CM01009

Inspection Description - ELECTRIC - RECONNECT

Inspection Status - Approved

Date Description Inspector Results Comments
03/22/2012 ELECTRIC - RECONNECT Approved OK TO CLEAR AND APPROVE PERMIT PER CONVERSATION OVER THE PHONE WITH R. MORENO ON 03/22/12 AT 12:26 PM
03/20/2012 ELECTRIC - RECONNECT Partial Approval IVRS - Inspection :*
03/19/2012 ELECTRIC - RECONNECT Denied IVRS - Inspection :
Work is not complete enough to inspect.| 950*
1) NO WORK PROGRESS
03/13/2012 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) BOX AT CEILING NOT INSTALLED PER CODE
2) RECEPTS ON INDUSTRIAL COVERS MISSING SCREWS
3) VERIFY PERMITS FOR BATHROOM REMODEL
4) CONDUCTORS NEED TO BE MARKED FOR HIGH LEG AFTER FUSES TO PANEL
5) LABEL PANEL WITH WARNING LABELS FOR HIGH LEG PER CODE