Permit: T12CM00967

Parcel: 118040810

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Permit Number - T12CM00967

Inspection Description - BUILDING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/21/2013 BUILDING - FINAL Approved IVRS - Inspection :*
10/18/2013 BUILDING - FINAL Cancelled IVRS - RI canceled
10/15/2013 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
10/15/2013 BUILDING - FINAL Denied 1. PAINT ROOF CENTS ABS
2. PROVIDE 1" CLEARANCE COMBUSTIBLES FROM B-VENT @ WATER HEATER
3. DRIP LEG WATER HEATER
4. A/C WHITE HOT LEAD TO BE BLACK OR RED (TAPE OK)
5. INTERCONNECT SMOKE ALARMS
6. LIGHT FIXTURE WHITHIN 12" OF SHELVES IN CLOSET
7. MISSING 110 GFCI OUTLET @ ROOF TOP
8. ARC FAULT PROTECT BEDROOM OUTLET