Permit: T12CM00965

Parcel: 12111206A


Addresses:

4902 E PIMA ST


Inspection Status: Approved

Inspection History: BUILDING - FINAL

Permit Number - T12CM00965

Inspection Description - BUILDING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/23/2012 BUILDING - FINAL Approved IVRS - Inspection :*
06/29/2012 BUILDING - FINAL Partial Approval IVRS - Inspection :*
TESTED HEAT SENSOR
PLANS REQUIRE ENTIRE DUCT TO BE WRAPPED. FIRE WRAP IS NOT BANDED PER INSTALL INSTRUCTIONS
PROVIDE A STEEL PLATE AT TOP OF GREASE DUCT
SECURE DISCONNECT ON ROOF
AIR BALANCE OK
06/28/2012 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
NO CONTRACTOR ON SITE
NEED TO SEE FIRE WRAP, MAKE UP AIR DUCTING, HEAT SENSOR TEST, CAPTURE & CONTAINMENT TEST AIR BALANCE REPORT ALL ROOF TOP EQUIPMENT