Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T12CM00964
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/29/2012 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 06/26/2012 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 06/22/2012 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1ST LAYER FIRE WRAP ON SECTION BELOW SHAFT ROCK OK OK FRO 2ND LAYER PROVIDE SMOKE ? FOR CONTAINMENT TEST |
|
| 06/19/2012 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 05/24/2012 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) 2ND LAYER OK, OK TO INSTALL DUCT |
|
| 05/22/2012 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) 1ST LAYER FIRE WRAP OK, OK 2ND LAYER |
|
| 05/18/2012 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) SMOKE/LEAK TEST ON 5' LENGTH OF GREASE DUCT, OK 1ST LAYER 2) PROVIDE APPROVED DUCT WRAP |
|
| 05/16/2012 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) DUCT ON TYPE I HOOD DOES NOT MEET MINIMUM CODE REQUIREMENTS 2) PROVIDE SMOKE/LEAK TEST PRIOR TO WRAP |