Permit: T12CM00958

Parcel: 11449042Q


Addresses:

2400 N PANTANO RD

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
05/04/2012 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
05/03/2012 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
1) UNABLE TO LOCATE TEST GAUGE
2) REQUIRE 10 POUND TEST ON ENTIRE SYSTEM, DO NOT TEST THRU ANSUL VALVES. WILL REQUIRE SIGNS SHOWING LOCATION OF ANSUL VALVES
3) OPEN CEILING TO EXPOSE GAS PIPING
4) PROVIDE LADDER
NOTE:
INSPECTOR NOTICED SEVERAL INSANITARY CONDITIONS, MOST NOTABLY INDIRECT WASTE PIPING AND BACK FLOW PROTECTION. I.W. PIPING TO BE GRAVITY DRAIN, OF APPROVED MATERIALS AND MUST HAVE AT LEAST 1" AIR GAP. EACH WATER SUPPLICED DEVICE TO HAVE IT'S OWN BACKFLOW PROTECTION. NO SPLITTING DOWNSTREAM
05/01/2012 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
1) PROVIDE FULL SIZED PIPING TO BRAZING PAN
2) TEST FOR FINAL
3) COMPLETE ALL WORK SHOWN ON PLAN
4) INSTALL BEV EQUIPMENT
5) PROVIDE BACKFLOW CERTS
6) CORRECT HS P TRAPS IN BACKWARDS
7) AIR GAPS FOR INDIRECT DRAINS