Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
Permit Number - T12CM00926
Inspection Description - ELECTRIC - RECONNECT
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/20/2012 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
03/08/2012 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SMOKE DETECTORS REQUIRED IN BEDROOMS 2) REPLACE DISCONNECT SWITCH FOR FURNACE 3) COVERS MISSING TO OUTSIDE RECEPTS 4) SUPPORT CONDUITS TO AC UNIT AT DISCONNECT AND SERVICE PANEL. RESUPPORT SUB PANEL, PVC CONDUIT NOT TO CODE 5) ISOLATE GROUNDS AND NEUTRALS IN SUB PANEL 6) ENCLOSED CARPORT WIRING NOT TO CODE, NO RECORD OF PERMIT FOR SUCH |