Permit: T12CM00905

Parcel: 107120960


Addresses:

267 E LAGUNA ST


Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Permit Number - T12CM00905

Inspection Description - ELECTRIC - RECONNECT

Inspection Status - Approved

Date Description Inspector Results Comments
04/30/2012 ELECTRIC - RECONNECT Approved IVRS - Inspection :*
04/27/2012 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) USE CURRENT SIZED CONDUIT STRAPS
2) CORRECTLY IDENTIFY GROUNDED CONDUCTOR
3) MISSING BATHROOM LIGHT
4) FINISH ALL PREVIOUS ITEMS 1, 2, 4 & 11
5) A REFEE MAY BE ASESSED IF NOT COMPLETED BY NEXT INSPECTION
04/19/2012 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
03/08/2012 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ELECTRIC PANEL TO BE UNLOCKED FOR INSPECTION (CONTACT TEP)
2) BARE WIRING AT PANEL TO BE REMOVED OR INSTALLED IN WEATHER PROOF BOX
3) WATER LINE BONDING (ALL GROUNDING) HAS BEEN REMOVED, NEEDS TO BE REPLACED
4) EXTERIOR OUTLETS AND CONDUIT ARE TO BE ANCHORED TO STRUCTURE
5) PLASTIC CONDUIT ON WEST SIDE OF HOUSE NOT ANCHORED TO STRUCTURE
6) WALL OUTLET IN STEP DOWN ROOM NEEDS REPAIR
7) LIGHT FIXTURE AT SHELF (ABOVE LAUNDRY) TO HAVE SAFETY GLOBE OR BE REMOVED
8) BARE WIRES IN BEDROOM CEILING
9) ELECTRIC SUB PANEL IN COMPLETE DISREPAIR (IN MECH. ROOM)
10) OUTLETS ABOVE KITCHEN COUNTER ARE TO BE GFI PROTECTED
11) THIS IS AN UNGROUNDED SYSTEM, ALL OUTLETS EXCEPT GFI ARE TO BE 2 PRONG UNGROUNDED OUTLETS