Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/22/2012 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 05/16/2012 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) BOND GROUNDING ELECTRODE TO CODE 250.64 AND LINE SIDE TO 1ST DISCONNECTING MEANS 2) CHASE NIPPLES ON PANEL MISSING, LINE AND LOAD MAYBE ENERGIZED, LABEL TO BE MADE DURABLE TO TAKE THE ELEMENTS 4) COMBINER TO BE MOVED AWAY FROM FIREPLACE CHIMNEY STACK ON ROOF |