Permit: T12CM00845

Parcel: 11005014C


Addresses:

2990 N SWAN RD


Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T12CM00845

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/19/2013 FIRE - FINAL Approved This permit covered 2nd floor deck remodel
07/16/2012 FIRE - FINAL Denied Under the 2006 ed. of the International Fire Code section 1003.6 Means of egress continuity - 1008.2 Gates - 1008.1.8.3 Locks and latches. All gates exiting out of the patio area are being chain and padlocked at night this is not allowed only approved locking devices are allowed on gates for the general public to use. All FD key boxes do not have keys to operate the pad locks or double cylinder keyed dead bolt locks being use on gates this is not allowed remove chain and padlocks and repair or replace double cylinder keyed dead bolt locks with thumb style dead bolt locks so as the public can open gates to leave property and keep keys in FD key boxes up to date.