Permit: T12CM00836

Parcel: 13419042A


Addresses:

7120 E BROADWAY BL

Inspection Status: Approved

Inspection History: FIRE - FINAL

Date Description Inspector Results Comments
10/16/2012 FIRE - FINAL Approved
08/06/2012 FIRE - FINAL Denied Need separate plan and permit for underground fire line.
Need to cover all ductile piping with plastic wrap and protect ductile from poured cement against the elbow, still need to do 200 psi test for 2 hours.