Permit: T12CM00836

Parcel: 13419042A


Addresses:

7120 E BROADWAY BL


Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Permit Number - T12CM00836

Inspection Description - FIRE SPKLR - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/16/2012 FIRE SPKLR - FINAL Approved
08/15/2012 FIRE SPKLR - FINAL Partial Approval PERMIT PULLED AND UG WAS PSI AND FLUSHED ALL PASSED
08/15/2012 FIRE SPKLR - FINAL Partial Approval NEED TO REMOVE ALL TAPED OFF OF SPRINKLERS AND INSULATION OFF OF SPRINKLER HEADS
08/06/2012 FIRE SPKLR - FINAL Denied Need separate plan and permit for underground fire line.
Need to cover all ductile piping with plastic wrap and protect ductile from poured cement against the elbow, still need to do 200 psi test for 2 hours.