Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T12CM00789

Parcel: 14029037D

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T12CM00789

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/01/2012 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/25/2012 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) ALL GROUNDING AT MAIN PANEL COMPLETE
05/24/2012 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) BOND NEUTRAL AT SERVICE MAIN DISCONNECT, NO PARALLEL GROUND FAULT RETURN 250 NEC
2) OK 2-GROUND RODS
3) G.E. SYSTEM TO BE COMMON FOR MULTI SERVICES ON SAME BLDG PER 250.58-#4 PER 250.66
4) OK TRANSFORMER, BONDING AND PANELS IN BLDG
05/23/2012 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) RESCHEDULE INSPECTION AND HAVE ELECTRIC CONTRACTOR ON SITE TO OPEN EQUIP.
2) EXPOSE GROUNDING AT SERVICE