Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T12CM00789
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/01/2012 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
05/25/2012 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) ALL GROUNDING AT MAIN PANEL COMPLETE |
|
05/24/2012 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) BOND NEUTRAL AT SERVICE MAIN DISCONNECT, NO PARALLEL GROUND FAULT RETURN 250 NEC 2) OK 2-GROUND RODS 3) G.E. SYSTEM TO BE COMMON FOR MULTI SERVICES ON SAME BLDG PER 250.58-#4 PER 250.66 4) OK TRANSFORMER, BONDING AND PANELS IN BLDG |
|