Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit: T12CM00724

Parcel: 11108314B


Addresses:

2460 N DODGE BL

Inspection Status: Approved

Inspection History: ELECTRIC - OUTDOOR LIGHTING

Date Description Inspector Results Comments
06/11/2012 ELECTRIC - OUTDOOR LIGHTING Approved IVRS - Inspection :*
05/08/2012 ELECTRIC - OUTDOOR LIGHTING Partial Approval IVRS - Inspection :*
1) BOND SUPLIMENTAL ELECTRODE CONDUCTOR AND EQUIPMENT GROUNDING CONDUCTOR
2) PROTECT CONDUCTORS 352.46 & 300.4
3) SPLICES TO BE FOR WET LOCATION
4) SPLIT BOLT LISTED FOR RUN AND TAP ONLY
5) EAST LIGHT POLE ON BACK ORDER
04/04/2012 ELECTRIC - OUTDOOR LIGHTING Partial Approval IVRS - Inspection :*
04/03/2012 ELECTRIC - OUTDOOR LIGHTING Not ready for Inspection IVRS - Inspection :*