Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T12CM00724

Parcel: 11108314B


Addresses:

2460 N DODGE BL

Inspection Status: Approved

Inspection History: ELECTRIC - OUTDOOR LIGHTING

Date Description Inspector Results Comments
06/11/2012 ELECTRIC - OUTDOOR LIGHTING Approved IVRS - Inspection :*
05/08/2012 ELECTRIC - OUTDOOR LIGHTING Partial Approval IVRS - Inspection :*
1) BOND SUPLIMENTAL ELECTRODE CONDUCTOR AND EQUIPMENT GROUNDING CONDUCTOR
2) PROTECT CONDUCTORS 352.46 & 300.4
3) SPLICES TO BE FOR WET LOCATION
4) SPLIT BOLT LISTED FOR RUN AND TAP ONLY
5) EAST LIGHT POLE ON BACK ORDER
04/04/2012 ELECTRIC - OUTDOOR LIGHTING Partial Approval IVRS - Inspection :*
04/03/2012 ELECTRIC - OUTDOOR LIGHTING Not ready for Inspection IVRS - Inspection :*