Inspection History: FIRE - ALARM FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/06/2013 | FIRE - ALARM FINAL | Approved | ||
| 03/05/2013 | FIRE - ALARM FINAL | Partial Approval | No troubles showing on FACP | |
| 02/26/2013 | FIRE - ALARM FINAL | Partial Approval | Roof top need to test duct smoke detectors x 2 Test new flow switches added at the main OS&Y All breakers for NAC's and FACP need lock outs Need date of install on all batteries for NAC's and FACP Correct tamper switches in fire pump room - two tampers for by-pass did not work. |