Permit: T12CM00713

Parcel: 129090410


Addresses:

1518 E 25TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Date Description Inspector Results Comments
03/27/2012 ELECTRIC - RECONNECT Approved IVRS - Inspection :*
03/12/2012 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) RELOCATE SMOKE ALARMS PER SPECS IN BEDROOMS
2) PROTECT ROMEX IN LAUNDRY ROOM UNDER 7' IN HEIGHT FROM PHYSICAL DAMAGE
3) EXPOSED 220 CONDUCTORS LAUNDRY ROOM
4) BEDROOM WINDOWS DO NOT MEET MINIMUM OPENING 20" X 24" AND BARS DO NOT OPEN FOR EMERGENCY EGRESS OR INGRESS
5) NOTES 1-3 FOR POWER
03/09/2012 ELECTRIC - RECONNECT Not ready for Inspection IVRS - Inspection :*
1) LEFT MSG. 8:10 AM
2) NO ACCESS 8:40 AM
03/08/2012 ELECTRIC - RECONNECT Not ready for Inspection IVRS - Inspection :*
1) PROVIDE ACCESS
03/01/2012 ELECTRIC - RECONNECT Partial Approval IVRS - Inspection :*
1) MISSING COVER PLATE RECEPT UNDER PANEL
2) SMOKE DETECTORS NEEDED HALL AND BEDROOMS