Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
03/02/2012 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
02/28/2012 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ON LINE SIDE BOND BUSHING MISSING
2) PLASTIC BUSHING ON BACK OF PANEL FOR BRANCH CIRCUIT WIRES MISSING
3) CHASE NIPPLE ON LB ON BOTTOM OF PANEL HAS LOCK NUT MISSING
4) ADDRESS LABEL MISSING
5) 2 GROUND RODS MISSING
6) WATER AND GAS BOND MISSING
7) LOW VOLTAGE BUSHINGS MISSING UNDER PANEL