Permit: T12CM00645

Parcel: 114517010


Addresses:

8802 E HONEYBEAR PL

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
05/17/2012 BUILDING - FINAL Approved IVRS - Inspection :*
05/07/2012 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CALCULATION FOR AND CODE RFERENCES FOR UNDER SIZED NEUTRALS TO GO TO PLANS EXAMINER RAY MAJUTA FIRST
2) LADDER NEEDED FOR ROOF INSPECTION
05/02/2012 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*
04/27/2012 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
ROOF:
1) SUPPORT HANGING PV CABLES
2) GROUNDING TO BE DISCUSSED WITH TIM
3) SEAL ROOF PENETRATIONS PER ROOFING ASSOC. FLASHING REQUIREMENTS
HOUSE:
1) LABELING PER 690.17
2) GROUNDING ELECTRODE CONDUCTORS 250.64
3) PLEASE VERIFY CODE SECTION FOR GROUNDED CONDUCTOR SIZING
04/25/2012 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) INSTALL NOT COMPLETE: A/C DISCONNECT TO PANEL MISSING, LABELS MISSING AND LADDER MISSING