Permit: T12CM00630

Parcel: 12709016A

Inspection Status: Approved

Inspection History: FIRE - FINAL

Date Description Inspector Results Comments
03/14/2013 FIRE - FINAL Approved
03/12/2013 FIRE - FINAL Correction Required Provide upright sprinkler coverage thought-out sales floor area, due to walls not full height to deck in the storage areas or show another alterative. Fire in the storage can get above sprinkler coverage in the sales area due to sprinkler coverage is now pendent style for the drop ceiling and non-combustible constriction requirements.