Permit: T12CM00614

Parcel: 130110600


Addresses:

2011 S HOWARD SV

Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Date Description Inspector Results Comments
03/29/2012 ELECTRIC - RECONNECT Approved IVRS - Inspection :*
02/24/2012 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SECURITY LIGHT IN CARPORT HAS OPEN CONNECTOR COVER LOOSE
2) EXPOSED WIRING/SPLICES AT SERVICE PANEL NOT TO CODE. PANEL COVER MISSING HINGE, PVC CONDUIT NOT TO CODE, COVERS J-BOX COVER AND IS NOT INSTALLLED PROPERLY
3) ROMEX NOT SUPPORTED PER CODE
4) COOLER SWITCH HANGING FROM CEILING
5) SMOKE DETECTORS REQUIRED IN ALL BEDROOMS
6) RECEPT ON WALL, SURFACE MTD, NOT CORRECT WIRING METHODS (RACEWAY NOT FOR ELECTRICAL WIRING) BY NORTH BEDROOM
7) OBTAIN THE SERVICES OF A LICENSED OR QUALIFIED ELECTRICIAN