Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - SERVICE UPGRADE
Permit Number - T12CM00599
Inspection Description - ELECTRIC - SERVICE UPGRADE
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/16/2012 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) WORK NOT DONE, A REFEE WILL BE ATTACHED TO THIS PERMIT IF ALL CORRECTIONS ARE NOT MADE PRIOR TO NEXT INSPECTION |
|
03/05/2012 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) VERIFY WATER/GAS PIPE BONDING 2) CANNOT USE ALL IN ONE WITH LISTING FOR SERVICE EQUIPMENT ONLY AS SUB PANEL 110.3 NEC 3) ALL CIRCUIT BREAKERS TO BE OF SAME MANUF. AS PANEL PER 110.3 NEC 4) PLUG ALL UNUSED OPENINGS |
|
02/27/2012 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) CALL FOR FINAL AFTER CUT OVER 2) NO LOADS CONNECTED YET 3) BE ADVISED, CONDUIT DEPTH 18" MINIMUM TOP OF CONDUIT TO FINISHED GRADE 300.5 NEC |
|
02/24/2012 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) BONDING TYPE FITTING REQUIRED ON SUPPLY SIDE 250.92 2) OK GROUND RODS |