Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/06/2012 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 04/05/2012 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) NO ACCESS/NO MSG. LEFT 2) PROVIDE ACCESS TO ROOF TOP UNIT 3) NEXT NOT READY MAY RESULT IN A REFEE |
|
| 04/04/2012 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) NO ACCESS TO UNIT 2) PROVIDE SAFE ACCESS TO ROOF 3) POST HOUSE NUMBERS VISIBLE FROM STREET |
|
| 03/30/2012 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) RTU DISCONNECT CANNOT BE MOUNTED ON ACCESS PANEL 2) PROVIDE ROOF JACK AND LIQUID TIGHT FITTINGS ON ELECT. EMT TO RTU 3) ALL PVC PIPE AND FITTINGS TO HAVE PRIMERED JOINTS, PRIMER TO BE APPLIED PRIOR TO GLUE 4) PROVIDE SERVICE OUTLET ON ROOF WITHIN 25' OF UNIT 5) WATER HEATER FLUE NOT PROPERLY INSTALLED 6) PROVIDE PLUG AT WATER HEATER PAN |
|
| 03/27/2012 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) EXTEND WATER HEATER FLUE 24" ABOVE UNIT NOT 10' FROM UNIT |