| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/04/2012 | ELECTRIC - SERVICE UPGRADE | Approved | ||
| 03/12/2012 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) WATER AND GAS BOND MISSING 2) GROUND RODS TO BE 6' APART 3) STRAP GROUNDING ELECTRODE UNDER PANEL 4) ON FINAL TO SEE BRANCH CIRCUIT LANDED |