Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T12CM00555

Parcel: 135110020


Addresses:

7534 E PALMA ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
04/04/2012 ELECTRIC - SERVICE UPGRADE Approved
03/12/2012 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*
1) WATER AND GAS BOND MISSING
2) GROUND RODS TO BE 6' APART
3) STRAP GROUNDING ELECTRODE UNDER PANEL
4) ON FINAL TO SEE BRANCH CIRCUIT LANDED