Permit: T12CM00553

Parcel: 113094650


Addresses:

1218 E GLENN ST #01

Inspection Status: Partial Approval

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
03/21/2012 BUILDING - FINAL Partial Approval IVRS - Inspection :*
1) BONDING FOR GEC IN METAL RACEWAY 250.64 (E)
03/13/2012 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PLANS NOT REFLECTIVE OF WORK INSTALLED-NEED REVISION
2) GROUNDING ELECTRODE CONDUCTOR TO BE 250.64 (E) TO INVERTER
3) SEPERATE GROUND AND GROUNDED CONDUCTOR AT A/C DISCONNECT
4) SECURE FRAME CONNECTIONS