Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - PROGRESS
Permit Number - T12CM00498
Inspection Description - PLUMBING - PROGRESS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/15/2014 | PLUMBING - PROGRESS | Approved | IVRS - Inspection :* | |
05/14/2013 | PLUMBING - PROGRESS | Not ready for Inspection | IVRS - Inspection :* | |
05/13/2013 | PLUMBING - PROGRESS | Not ready for Inspection | RED LINE ALL CHANGES MADE. INSTALL HOSE BIB VACUUM BREAKERS. PROVIDE STERILIZATION DOCUMENTATION. PROVIDE CERTS FOR INTERNAL BACKFLOW ASSEMBLIES. YARD WATER LINE HAS NOT BEEN INSPECTED. DOES NOT APPEAR TO BE DEEP ENOUGH AND HAS ROCKS TOUCHING. ISOLATE COPPER FROM METAL. TRIM OR SEAL ALL DWV IN BUILDING. PROVIDE A SMOOTH WALL SURFACE AT RELOCATED OF AND SEAL WALL TO WALL. NOTE: PARTIAL INSP ONLY. WATER HEATER NOT IN. LIGHTS OFF. LETTER RECEIVED FOR MATERIAL CHANGES & DELETION OF CARRIERS |
|
04/30/2013 | PLUMBING - PROGRESS | Not ready for Inspection | IVRS - Inspection :* | |
02/28/2013 | PLUMBING - PROGRESS | Partial Approval | IVRS - Inspection :* | |
02/26/2013 | PLUMBING - PROGRESS | Partial Approval | NOT INSTALLED PER PLAN PROVIDE DOCUMENTATION ALLOWING DELECTION OF LAVITORY CARRIERS SPECIFIED ALSO FOR CELLULAR CORE PVC CONTRARY TO PLAN SPECS CORRECT WATER AND VENT SIZE LINE REQ 1" INSULATION |