Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T12CM00483
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/03/2012 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/02/2012 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) LABEL ALL CIRCUITS AT PANEL 2) MEC 408.4 CIRCUITS MUST BE SPECIFICALLY IDENTIFIED (CANNOT USE GENERAL) 3) BRACE RACEWAY UNDER PANEL 4) PERMANENT IDENTIFICATION NEEDED FOR PARALLEL ENERGY SOURCE DISCONNECT 5) UNDERSIZED CONDUCTOR UNDER A 20 AMP BREAKER (DOWNSTAIRS) 6) ANTI-OXIDANT NEEDED ON ALUM. CONDUCTORS AT BREAKERS 7) LABEL NON METALIC PLUMBING AT PANEL |
|
| 03/01/2012 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) CALL FOR FINAL AFTER PANEL MAKE UP |