Inspection History: ELECTRIC - FINAL

Permit Number - T12CM00483

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/03/2012 ELECTRIC - FINAL Approved IVRS - Inspection :*
03/02/2012 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) LABEL ALL CIRCUITS AT PANEL
2) MEC 408.4 CIRCUITS MUST BE SPECIFICALLY IDENTIFIED (CANNOT USE GENERAL)
3) BRACE RACEWAY UNDER PANEL
4) PERMANENT IDENTIFICATION NEEDED FOR PARALLEL ENERGY SOURCE DISCONNECT
5) UNDERSIZED CONDUCTOR UNDER A 20 AMP BREAKER (DOWNSTAIRS)
6) ANTI-OXIDANT NEEDED ON ALUM. CONDUCTORS AT BREAKERS
7) LABEL NON METALIC PLUMBING AT PANEL
03/01/2012 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) CALL FOR FINAL AFTER PANEL MAKE UP