Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/22/2012 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/09/2012 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) MAINTAIN WORKING CLEARANCES 110.20 2) STRAP GROUNDS TO STRUCTURE 3) VERIFY DERATING OF CONDUCTORS PER 310.15 4) MAINTAIN CLEARANCE FROM EDGE OF POOL 680.10 (WILL BE TRANSFERED TO POOL PERMIT PER R. MAJUTA) |