Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T12CM00416
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/15/2012 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
03/07/2012 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) GEC'S TO BE PER 250.64 (E) 2) PROTECT AND SUPPORT PVC UP OUT OF SUB 3) PLEASE VERIFY LISTING FOR BRAIN BOX 4) CLEAN EXCESS FOREIGN MATERIAL AND DIRT FROM BOTTOM 6 X 6 BOX 5) LABEL DISCONNECT 6) IS PVC UNDER DRAIN AREAS 24" 300.5 |
|
02/28/2012 | ELECTRIC - INTERMEDIATE | Partial Approval | PEDISTAL BASE OK. MAKE UP TO SHED NOT DONE YET. MAY NEED TO CHANGE ADDRESS OF THIS ACTIVITY TO MATCH WATER DEPARTMENT ADDRESS. | |
02/17/2012 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK 3/4" PVC FROM EXISTING TO PULL BOX TO WALL 2) PHYSICALLY PROTECT #8 GEC |